32
Start-up
Type ME43
8.5 Protocol settings for connecting the device to the
PLC network
Therequiredsettingsdependontheeldbusprotocol.
Toensurethatthesettingscanbemade,theeldbusprotocolmustbeselectedintheparameter
detailedview:
Parameter → Protocol →Selectprotocol.
IfdevicesfeatureaPROFIBUSinterfaceandCC-Linkinterface,theeldbusprotocolhasbeen
presetatthefactory.
8.5.1 Setting the PROFIBUS address
PROFIBUSaddresspre-conguredatthefactory:126
The PROFIBUS address can be set on the display of the device or on the PC using the Bürkert Communi-
cator PC software.
The menu for setting the PROFIBUS address is located in the Parameter detailed view.
ChangetotheParameterdetailedview:
For the setting using the Bürkert Communicator in the navigation area, select Industrialcommunication.
To make the setting on the display, press the menu key
twice.
You are in the detailed view Parameter.
ThePROFIBUSaddresscanonlybesetwhentheeldbusprotocolPROFIBUS DPV1hasbeen
selected.IfdevicesfeatureaPROFIBUSinterface,theeldbusprotocolhasbeenpresetatthe
factory.
SettingthePROFIBUSaddress:
→ On the display select PROFIBUSaddress and input PROFIBUS address.
→ In the Bürkert Communicator select Protocolsettings → PROFIBUSaddress and input PROFIBUS
address.
→ Enter the address. Valid addresses: 0 to 126
If an address is set outside of the valid range, the device will display an error message.
You have set the PROFIBUS address to connect the device to the PLC network.
english