EasyManua.ls Logo

Burkert ME43 - Page 24

Burkert ME43
67 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
Start-up
Type ME43
Contextualizeddenitionofvalue:
Input values
Icon:
i
Input values are values which come from the büS participant and are read by the PLC (büS device
fieldbusgateway PLC)
Output values
Icon:
O
OutputvaluesarevalueswhicharewrittenfromthePLCtothebüSparticipant/eldbusgateway.
büSdevice
Outputvalue
Inputvalue
Inputvalue Outputvalue
Continued output data
Continued input data
Figure 10: Conguration; type of conversion for process values from the PLC to the büS device
2. Adjusting properties of the values:
Thepropertiesforthevaluesonlyrequireadjustmentifdeviationsfromthestandardare
requested.
In the overview click on the input value or output value to be declared.
The selected value is highlighted in grey.
The default values for the declaration are shown at bottom right.
Meaningofthedefaultvalues.
Thedefaultvaluesareusedwhenthedevicestartsorifthepartnerdevicewasnotfound.
For the declaration input or select the following:
Accept or adjust Name.Thesenamesappearviathedevicedescriptionleinthetargetcontrol.
Valuetype. Specify physical size or device status for the input or output.
Select or do not select Defaultvalue.
The standard value is accepted if no signal arrives from the partner device.
Select or do not select CANopencompatible.
Is selected when the values are consumed by a CANopen device.
Unitconversion.
SpeciesinwhichphysicalunitthevalueisreceivedorsentbythePLC.
YouhaveselectedanddeclaredtheinputsandoutputsfortheGatewayconguration.
Using Next,openthemenufortheeldbus-specicaddressmapping.
english

Table of Contents