62-11640 5–28
RAIL SETTINGS
UNIT OPERATION STANDARD
RAIL
RAIL = The system is set to control Rail refrigeration
operation. When this Configuration is set to “RAIL”
the following “VEHICLE ID”, “RAIL SHUTDOWN
OVERRIDE” and “RAIL OVERRIDE RESTARTS”
Sub-Configurations will be available.
VEHICLE ID ASSET
TRAILER
CAR
Modifies the prefix wording used for display of the
customer assigned ID number entered in the “TRAIL-
ER ID” Configuration. For example, if the customer
assigned ID number entered is 12345:
ASSET = will display “ASSET # 12345”
TRAILER = will display “TRAILER # 12345”
CAR = will display “CAR # 12345”
RAIL SHUTDOWN OVERRIDE NO
YES
NO = When the 00030 FAILED TO RUN MINIMUM
TIME or 00031 FAILED TO START - AUTO MODE
alarm is activated, the system will not override the
alarm(s) and the unit will not restart until the alarms
are cleared manually.
YES = When either an 00030 FAILED TO RUN MIN-
IMUM TIME or 00031 FAILED TO START - AUTO
MODE alarm is activated, the unit will automatically
override and clear the alarm(s) and attempt a restart
after 4 hours. When this Configuration is set to “YES”
the “RAIL OVERRIDE RESTARTS” Sub-Configura-
tions will be available.
RAIL OVERRIDE RESTARTS 1-20
3
With the default setting the system is allowed to over-
ride and clear the 00030 FAILED TO RUN MINIMUM
TIME or 00031 FAILED TO START - AUTO MODE
alarm(s) three consecutive times before the override
is locked out and no further restart attempts will be al-
lowed until the alarm(s) are cleared manually.
The number of restart attempts allowed before the
override is locked out may be changed by entering
the desired number in this Sub-Configuration. Set-
ting this number too high may result in a discharged
or damaged battery if the unit never actually starts or
fails to run long enough to charge the battery prior to
shutting down again.
Table 5–1 Configuration Settings
(Refer to Section 5.2.3 for instructions on entering Configuration settings)
Configuration Selections Description