Chapter 6 - Parameter Description
6-38
6.8 Communication Group [COM]
The communication option card manual provides a
detailed description of the installation, wiring and
set-up procedures.
1)**+B'1
COM-00 allows
jumping to any
parameter in COM group without scrolling to it.
Press [ENTER] key and put a desired parameter
code by using [SHIFT] and [UP]/[DOWN] keys.
When [ENTER] key is pressed again, the desired
parameter will be on the display.
1)*+ !;"
COM-01 shows what
type of communication
board is installed. There are five types of
communication boards: RS-485, DeviceNet,
ProfiBus, BACnet and LonWorks
1)*+ !;"1! "
COM-03 has four
selections for VFD
control via communication card: None, Command,
Freq and Cmd+Freq.
None- The communication provides only
monitoring of the VFD parameters but no control.
Command- The communication provides
monitoring of the VFD parameters and start/stop
control. The VFD speed control is based on SET-10
selection.
Freq- The communication provides monitoring of
the VFD parameters and speed control. The VFD
start/stop control is based on SET-09 selection.
Cmd+Freq- The communication provides
monitoring of the VFD parameters, start/stop and
speed control.
1)*.+ !;""!
COM-03 shows the
communication board
version number.
1)*+%1$
COM-10 allows to set
MAC ID from 0 to 63.
1)+;' 
COM-11 allows to set
Baud rate: 125, 250 or
500kbps.
1)+'$! !
COM-10 allows to set
Out Instance: 20, 21,
100 or 101.
1).+& $!' $! !
COM-13 allows to set
DeviceNet input
instance number: 70, 71, 110 or 111.
1)3+1 !  !$'8"
COM-17 allows to set
station ID number from
0 to 63.
1)*+">;'%1$'8"
COM-20 is a Profibus
station ID number from
1 to 127.
1).*+' ' '8"
COM-30 allows to set
output number from 0
to 8.
1).A.4+' ' %"<#?=
COM-31 through
COM-38 are
parameters for eight communication output address
settings.
COM
Jump Code
00 2
COM Opt
B/D
01 BACnet
COM Opt
Mode
02 None
COM Opt Version
03
Ver x.x
COM In Instance
13
70
COM Station ID
17
1
COM Profi MAC ID
20
1
COM Output Num
30
3
COM Output1
31
000A
COM MAC ID
10
63
COM Baud Rate
11
125 kbps
COM OutInstance
12
21