Chapter 5 – Parameter List
5-7
5.5 [FG1] Function Group 1 parameter group
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Adjust
Run
Page
FG1-00 9300 Jump to Desired Code # Jump Code
1 to 91
6-12
FG1-01 9302 Acceleration Pattern Acc. Pattern
0
(Linear)
1
(S-curve)
2
(U-curve)
FG1-02 9303 Deceleration Pattern Dec. Pattern
0
(Linear)
1
(S-curve)
2
(U-curve)
FG1-03
9304 Accel. S-Curve Ratio Start Curve 0 to 100 [%]
FG1-04 9305 Decel. S-Curve Ratio End Curve 0 to 100 [%]
FG1-10 930A Pre-Heat PreHeat Mode
0
(No)
1
(Yes)
FG1-11 930B Pre-Heat Value PreHeatLevel 1 to 50 [%]
6-13
FG1-12 930C Pre-Heat Duty Cycle PreHeatDuty 1 to 100 [%]
FG1-20 9314 Start Mode Start Mode
0 (Accel)
1 (Dc-start)
2 (Flying-start)
FG1-21
9315 DC Injection Start Time DcSt Time 0.0 to 60.0 [sec]
FG1-22 9316 DC Injection Start Value DcSt Value 0 to 150 [%]
FG1-24 9318 DC Injection Braking On-delay DcBr Delay 0.00 to 60.00 [sec]
FG1-25 9319 DC Injection Braking Frequency DcBr Freq 0.01 to 60.00 [Hz]
FG1-26 931A DC Injection Braking Time DcBr Time 1.0 to 60.0 [sec]
FG1-27 931B DC Injection Braking Value DcBr Value 0 to 200 [%]
FG1-28 931C Safety Stop Safety Stop
0
(No)
6-14
1
(Yes)
FG1-29 931D Power Source Freq Line Freq 40 to 120 [Hz]
FG1-30 931E Maximum Frequency Max Freq 40 to 120 [Hz]
FG1-31 931F Base Frequency Base Freq 30 to 120 [Hz]
FG1-32 9320 Starting Frequency Start Freq 0.01 to 10.00 [Hz]
FG1-40 9328 Volts/Hz Pattern V/F Pattern
0
(Linear)
1
(Square)
2
(User V/F)
FG1-41 9329 User V/F - Frequency 1 User Freq 1 0 to FG1-30
FG1-42 932A User V/F - Voltage 1 User Volt 1 0 to 100 [%]
FG1-43 932B User V/F - Frequency 2 User Freq 2 0.00 to FG1-30
FG1-44 932C User V/F - Voltage 2 User Volt 2 0 to 100 [%]
FG1-45 932D User V/F - Frequency 3 User Freq 3 0.00 to FG1-30
FG1-46 932E User V/F - Voltage 3 User Volt 3 0 to 100 [%]
FG1-47 932F User V/F - Frequency 4 User Freq 4 0.00 to FG1-30
FG1-48 9330 User V/F - Voltage 4 User Volt 4 0 to 100 [%]
FG1-51 9333 Energy Save Energy Save
0
(None)
6-15
1
(Manual)
2
(Auto)
FG1-52
9334 Energy Save % Manual Save% 0 to 30 [%]
FG1-54 9336 Integrating Wattmeter KiloWattHour M kWh
Display FG1-55 9337 Inverter Temperature Inv. Temp. 0 to 160 [°C]
FG1-56 9338 Motor Temperature Motor Temp. 0 to 160 [°C]
FG1-57 9339 No Motor Trip Selection No Motor Sel
0
(No)
6-15
1
(Yes)