Chapter 5 – Parameter List
5-3
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
SET-65 9141
Speed VFD ramps down to when Aux starts
MMC DecFreq
0 to FG1-30
SET-66 9142
MMC Feedback Start Differential
AuxStartDiff
0.0 to 100.0 [%]
SET-67 9143
MMC Feedback Stop Differential
AuxStopDiff
0.0 to 100.0 [%]
SET-74 914A
Under/Over Level Detection Mode Level Detect
0 (No)
6-8
1 (Under Level)
2 (Over Level)
SET-75 914B
Level Detection Mode Source LDT Source
0 (Current)
1 (DC Voltage)
2 (Output Voltage)
3 (kW)
4 (V1)
5 (I)
SET-76 914C
Level Detection Mode Frequency LDT Freq
0 to FG1-30 [Hz]
SET-77 914D
Level Detection Mode Delay Time LDT Delay
0 to 9999 [sec]
SET-78 914E
Level Detection Mode Level LDT Level
0 to 999.9 [Unit]
SET-79 914F
Level Detection Mode Hysteresis LDT Hyst
0 to 999.9 [Unit]
SET-80 9150 Level Detection mode Trip Setting LDT Trip
0 (No)
1 (Yes)
SET-81 9151 Level Detection Mode Well Fill Time LDT FillTime
0 to 3000.0 [min]
SET-82 9152 Level Detection Mode Output Relay LDT Relay
0 None
1 AUX_3
2 AUX_4
SET-90 915A
Local / Remote Key Operation Selection LocalRemKey
0 (2nd Source)
1 (Cntl&RefStop)
2 (Control Stop)
3 (Ref Only)
4 (Cntl&Ref Run)
5 (Control Run)
6 (Disabled)
5.2 [SET] Parameter Group Default Settings
CODE
LCD Keypad
Display
Basic
Supply
Fan
Exhaust
Fan
Cooling
Tower
Circul.
Pump
Subm.
Pump
Vacuum
Pump
Const.
Torq.
SET-00
App. Select Basic Supp. Fan Exh. Fan Cooling T Circ.Pump
Sub. Pump
Vacuum Const T
SET-01
Input Phase 3 3 3 3 3 3 3 3
SET-02
Motor HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
SET-03
Motor FLA
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
By VFD HP
SET-04
Motor RPM 1800 1800
1800
1800
1800
3600 3600
1800
SET-06
Carrier Freq
(400-700HP)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
1.0kHz
(1.0kHz)
2.5kHz
(2.0kHz)
2.5kHz
(2.0kHz)
SET-07
VAC 575.0V
VAC 480.0V
VAC240.0V
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
100%
109%
104.6%
SET-08
Motor Volt
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
575V
480V
230V
SET-09
Drive Mode Remote1 Remote1
Remote1
Remote1
Remote1
Keypad
Remote1
Remote1
SET-10
Speed Ctrl I I I Keypad1 Keypad1 Keypad1 Keypad1 Keypad1
SET-11
ACC Time
(150-700HP)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
20.0sec
(60.0sec)
2.0sec 30.0sec
(60.0sec)
20.0sec
(60.0sec)
SET-12
DEC Time
(150-700HP)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
30.0sec
(90.0sec)
10.0sec
(20.0sec)
120.0sec 30.0sec
(90.0sec)
SET-13
Low Limit
20.00Hz 20.00Hz 20.00Hz 20.00Hz 30.00Hz 30.00Hz 30.00Hz 10.00Hz
SET-14
High Limit 60.00Hz 60.00Hz 60.00Hz 60.00Hz 60.00Hz 60.00Hz 60.00Hz 60.00Hz
SET-15
Run Prev.
Reverse Reverse Reverse Reverse Reverse Reverse Reverse None
SET-16
Stop Mode Coast Coast Coast Coast Decel Decel Coast Decel
SET-20
PID Mode No No No Yes Yes Yes Yes No