Chapter 5 – Parameter List
5-10
5.7 [FG2] Function Group 2 parameter group
CODE
Com.
Addr
Description
LCD Keypad
Display
Setting Range
Run
Adj.
Page
FG2-00 9400 Jump to Desired Code # Jump Code
1 to 95
6-18
FG2-01 9401 Last trip 1 Last Trip-1 Press [ENTER] then
key to see Hz,
Amps,
Mode and trip
time then [ENTER]
Display
FG2-02 9402 Last trip 2 Last Trip-2
FG2-03 9403 Last trip 3 Last Trip-3
FG2-04 9404 Last trip 4 Last Trip-4
FG2-05 9405 Last trip 5 Last Trip-5
FG2-06 9406 Erase trips Erase Trips
0
(No)
1
(Yes)
FG2-07 9407 Last Trip Time LastTripTime X:XX:XX:XX:XX:X
Display
FG2-08 9408 Power On Time On-Time X:XX:XX:XX:XX:X
FG2-09 9409 Run-time Run-Time X:XX:XX:XX:XX:X
FG2-10 940A Dwell Time Dwell Time 0 to 6000 [sec]
FG2-11 940B Dwell/ Sleep Boost Frequency Dwell Freq FG1-32 to FG1-30
FG2-12 940C Jump Frequency Selection Jump Freq
0
(No)
1
(Yes)
FG2-13 940D Jump Frequency 1 Low Jump Low 1 FG1-32 to FG2-14
FG2-14 940E Jump Frequency 1 High Jump High 1 FG2-13 to Max
FG2-15 940F Jump Frequency 2 Low Jump Low 2 FG1-32 to FG2-16
FG2-16 9410 Jump Frequency 2 High Jump High 2 FG2-15 to Max
FG2-17 9411 Jump Frequency 3 Low Jump Low 3 FG1-32 to FG2-18
FG2-18 9412 Jump Frequency 3 High Jump High 3 FG2-17 to Max
FG2-19 9413 Power ON Start Selection Power On Run
0
(No)
6-19
1
(Yes)
FG2-20 9414 Start Delay Time after Power Up PwrUpRun Dly 0 to 9999 sec
FG2-21 9415 Restart after Fault Reset RST Restart
0
(No)
1
(Yes)
FG2-22 9416 IPF Mode IPF Mode
0
(No)
1
(Yes)
FG2-24 9418 Retry Selection Retry Mode
0
(No)
1
(Yes)
FG2-25 9419 Number of Auto Retry Retry Number 0 to 10
FG2-26 941A Delay Time Before Auto Retry Retry Delay 0 to 6000 [sec]
FG2-27 941B Flying Start Level FlySt Level 50 to160 [%]
FG2-30 941C Flying Start Mode FlySt Mode
0
(No)
1
(Yes)
FG2-42 942A Rated Motor Slip RPM Rated Slip
0 to 16% of motor
RPM
FG2-44 942C No Load Motor Current (RMS) Noload Curr 0.5 to 999.9 [A]
FG2-46 942E Load Inertia InertiaRate 1 to 40
6-20
FG2-47 942F Scale for Motor Speed Display RPM Scale 1 to 1000 [%]
FG2-49 9430 PWM Type Selection PWM Mode
0
(Normal )
1
(Low leakage)
FG2-50 9432 Safety Stop Decel Time Safety Time 1.0~100.0
FG2-51 9433 Safety Stop Gain SafetyGain 2~500
FG2-60 943C Control Mode Selection Control Mode
0
(V/F)
1
(Slip compen)
2
(Sensorless)