Chapter 5 – Parameter List
5-18
CODE
LCD Keypad
Display
Basic
Supply
Fan
Exhaust
Fan
Cooling
Tower
Circul.
Pump
Subm.
Pump
Vacuum
Pump
Const.
Torq.
I/O-72
S1 Mode
1 (Current) 1 (Current) 1 (Current) 1 (Current) 1 (Current) 1 (Current) 1 (Current) 1 (Current)
I/O-73
S1 Adjust
100 [%] 100 [%] 100 [%] 100 [%] 100 [%] 100 [%] 100 [%] 100 [%]
I/O-74
FDT Freq
1.00 [Hz] 1.00 [Hz] 1.00 [Hz] 1.00 [Hz] 1.00 [Hz] 1.00 [Hz] 1.00 [Hz] 1.00 [Hz]
I/O-75
FDT Band
I/O-76
Aux Relay1
13 (Run) 13 (Run) 13 (Run) 13 (Run) 13 (Run) 13 (Run) 13 (Run) 13 (Run)
I/O-77
Aux Relay2
0 (NONE) 10 (Damper)
10 (Damper)
10 (Damper) 0 (NONE) 0 (NONE) 0 (NONE) 0 (NONE)
I/O-78
Aux Relay3
I/O-79
Aux Relay4
4 (FDT-4) 4 (FDT-4) 4 (FDT-4) 4 (FDT-4) 4 (FDT-4) 4 (FDT-4) 4 (FDT-4) 4 (FDT-4)
I/O-80
FltRelayMode
100 [bit] 100 [bit] 100 [bit] 100 [bit] 100 [bit] 100 [bit] 100 [bit] 100 [bit]
I/O-82
RelayOnDly
0[sec] 0[sec] 0[sec] 0[sec] 0[sec] 0[sec] 0[sec] 0[sec]
I/O-83
RelayOffDly
0[sec] 0[sec] 0[sec] 0[sec] 0[sec] 0[sec] 0[sec] 0[sec]
I/O-84
Fan Control
0 (Power On)
0 (Power On)
0 (Power On)
0 (Power On)
0 (Power On)
0 (Power On)
0 (Power On)
0 (Power On)
I/O-85
Fan Temp
70 [C] 70 [C] 70 [C] 70 [C] 70 [C] 70 [C] 70 [C] 70 [C]
I/O-90
Inv No.
1 1 1 1 1 1 1 1
I/O-91
Baud Rate
3 (9600 bps) 3 (9600 bps) 3 (9600 bps) 3 (9600 bps) 3 (9600 bps) 3 (9600 bps) 3 (9600 bps) 3 (9600 bps)
I/O-92
Com Lost Cmd
0 (Hold)) 0 (Hold)) 0 (Hold)) 0 (Hold)) 0 (Hold)) 0 (Hold)) 0 (Hold)) 0 (Hold))
I/O-93
COM Time Out
1.0 [sec] 1.0 [sec] 1.0 [sec] 1.0 [sec] 1.0 [sec] 1.0 [sec] 1.0 [sec] 1.0 [sec]
I/O-94
Delay Time
I/O-95
In No/Nc Set
00000000000
00000000000
00000000000
00000000000
00000000000
00000000000
00000000000
00000000000
I/O-97
OH Trip Sel
010 [bit]
010 [bit] 010 [bit] 010 [bit] 010 [bit] 010 [bit] 010 [bit] 010 [bit]
I/O-98
MotTripTemp.
110 [°C]
110 [°C] 110 [°C] 110 [°C] 110 [°C] 110 [°C] 110 [°C] 110 [°C]