Chapter 6 - Parameter Description
6-9
)5*+ @'! !
The SET-90 parameter
has seven selections: 2
nd
Source, Cntl&RefStop, Control Stop, Ref Only,
Cntl&RefRun, Control Run, Disabled.
2
nd
Source- changes control to a second source
determined by parameters DRV-91 & DRV-92.
Cntl&Ref Stop- when Local/Remote Key is
pressed while VFD is running in remote control,
the VFD will stop the motor and switch
Command and Speed control to keypad.
Control Stop- when Local/Remote Key is
pressed while VFD is running in remote control,
the VFD will stop the motor and switch
Command control to keypad leaving remote
Speed control.
Ref Only- when Local/Remote Key is pressed
while VFD is running in remote control, the
VFD will switch Speed control to keypad and
continue running motor based on remote
Command control.
Cntl&Ref Run- when Local/Remote Key is
pressed while VFD is running in remote control,
the VFD will continue to run motor and switch
Command and Speed control to keypad.
Control Run- when Local/Remote Key is
pressed while VFD is running in remote control,
the VFD will continue to run motor and switch
Command control to keypad leaving remote
Speed control.
Disabled- pressing the Local/Remote Key will
not change VFD control (Local/Remote Key is
disabled).
SET
LocalRemKey
90 Cntl&RefStop