6-31
Cisco ASR 1000 Series Aggregation Services Routers Hardware Installation Guide
OL-13208-11
Chapter 6 Cisco ASR 1006 Router Overview and Installation
Connecting Power to the Cisco ASR 1006 Router
Figure 6-22 shows the ASR1013/06-PWR-DC power supply for the Cisco ASR 1006 Router.
Figure 6-22 Cisco ASR 1006 Router DC Power Supply (ASR1013/06-PWR-DC) Terminal Block Ground Cable Lugs
Step 6
For easier cable management, insert the negative lead cable first. Replace the ground lug with cable in
the following order:
a. Flat Washer
b. Ground lug with negative wire
c. Kepnut screw
Step 7 Tighten the Kepnut screw to recommended torque of 18 in-lbs minimum to 22 in-lbs maximum for the
positive stud and wire.
Note Secure the wires coming in from the terminal block so that they cannot be disturbed by casual contact.
Step 8 Use tie wraps to secure the wires, so that the wires are not pulled from the terminal block by casual
contact. Ti-wrap studs are located below the power supply terminal block (see Figure 6-23).
Step 9 Replace the terminal block plastic cover and tighten the screw. The plastic cover is slotted and keyed to
fit correctly over the terminal block.
1 Negative lug and wire with sleeving wrapped
around the wire and end of lug
3 Location of sleeving wrapped around the
wire and end of the grounding stud
2 Positive lug and wire with sleeving wrapped
around the wire and end of lug
4 Ground lug and wire
OUTPUT INPUT FAN
FAIL OK OK
ALARMS
60V
1A MAX
This unit might have more than one power supply connection. All connections must be removed to de-energize the unit.
-48/-60V 40A
253913
1 2
4
3