InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
158
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for start in absolute mode. i.e.
Pwr mgmt mode = ABS (kW) or ABS (kVA) if the reserve set #3 is active.
Learn more about reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
If the absolute power management is selected, this setpoint (or the setpoints
LoadResStrt 1, LoadResStrt 2 or LoadResStrt 4 depending on which load
reserve set is selected) determines also the number of gensets (that are part
of the power management) which will start (according to their priority and
nominal power).
NOTE:
There is a possiblity to assign this setpoint negative number. This can be
used in some situations to allow genset start after Sys Start/Stop gets active.
It is not destined for normal operation. Please refer to the Troubleshooting
guide for more information (chapter "MGCB is not closed although gensets
are running").
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.
12.2.8.11 Setpoint: #LoadResStop 3
Group
Pwr Management
Range [units]
LoadResStrt 3 .. 32000 [kX]
Related FW
3.0
Description
This setpoint is used to adjust the load reserve for stop in absolute mode. i.e.
Pwr mgmt mode = ABS (kW) or ABS (kVA) if the reserve set #3 is active.
Learn more about reserves in the chapter Reserves, minimal running power.
The currently active reserve set is selected by binary inputs Load res 2, Load
res 3 and Load res 4. If none of these inputs is active the set #1 is selected.
NOTE:
The reserve for stop must be always adjusted higher than the reserve for
start.
NOTE:
# sign in the name of this setpoint marks that this setpoint is shared among
all controllers connected by CAN2 bus.

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals