InteliMains
NT
, SW version 3.0
InteliMains-NT-BTB-3.0-Reference Guide.pdf, ©ComAp June 2013
208
The "cos-phi" factor is widely used instead of power factor for pure harmonic
waveforms, because a simplified method can be used for calculation of it's
value. However, if this simplified method is used for significantly distorted
waveforms, it may provide inaccurate results. This fact causes the controller
"power factor" value may be different from a value measured by another true-
rms measurement device if the waveform contains significant portion of
higher harmonic frequencies.
13.1.1.14 Value: BusL Ld char
Group
BusL values
Units
-
Related FW
3.0
Description
Character of the BusL load. "L" means inductive load, "C" is capacitive and
"R" is resistive load (power factor = 1).
13.1.1.15 Value: BLPf L1
Group
BusL values
Units
-
Related FW
3.0
Description
BusL power factor in phase L1.
13.1.1.16 Value: BL Ld char L1
Group
BusL values
Units
-
Related FW
3.0
Description
Character of the BusL load in the L1 phase. "L" means inductive load, "C" is
capacitive and "R" is resistive load (power factor = 1).
13.1.1.17 Value: BLPf L2
Group
BusL values
Units
-
Related FW
3.0

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals