Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position plays active role in the power management. Bit 0
represents address 17 etc. This value contains information about controllers
with addresses 17-32.
13.1.12.10 Value: GL16
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position has GCB closed. Bit 0 represents address 1 etc. This
value contains information about controllers with addresses 1-16.
13.1.12.11 Value: GL32
Group
Info
Units
-
Related FW
3.0
Description
Bits of this value show "1" if the controller which has address corresponding
with the bit position has GCB closed. Bit 0 represents address 1 etc. This
value contains information about controllers with addresses 17-32.
13.1.12.12 Value: Breaker state
Group
Info
Units
-
Related FW
3.0
Description
Code of the current state of the breaker control. The text representation of
each code can be obtained by the procedure described at the value Timer
text.
13.1.12.13 Value: Timer text
Group
Info
Units
-

Table of Contents

Other manuals for ComAp IGS-NT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IGS-NT Series and is the answer not in the manual?

ComAp IGS-NT Series Specifications

General IconGeneral
BrandComAp
ModelIGS-NT Series
CategoryController
LanguageEnglish

Related product manuals