15.2.1.41 Binary output: MODES: Aut mode
The output is closed while the controller is currently in AUT mode (either
switched by the mode selector on the front panel or by the input Remote
AUT).
15.2.1.42 Binary output: MODES: Off mode
The output is closed while the controller is currently in OFF mode (either
switched by the mode selector on the front panel or by the input Remote
OFF).
15.2.1.43 Binary output: MODES: Man mode
The output is closed while the controller is currently in MAN mode (either
switched by the mode selector on the front panel or by the input Remote
MAN).
15.2.1.44 Binary output: MODES: Aut mode
The output is closed while the controller is currently in AUT mode (either
switched by the mode selector on the front panel or by the input Remote
AUT).
15.2.1.45 Binary output: BusL Params OK
This output indicates that the BusL is healthy. The output is closed while all
BusL electrical parameters are in limits. If BTB is closed, the output
deactivates after the the delay for fixed voltage or frequency protections
elapses. If BTB is opened, the output deactivates immediately after electrical
parameters get out of limit (e.g. frequency, voltage, voltage unbalance etc.).