ID–Lite-2.0 User guide, ©ComAp – January 2011 25
ID-Lite-2.0 User guide.pdf
switched to MAN. Panel STOP button has no effect when Rem start/stop is closed in AUT but skip the
timer and switch to cooling when Rem start/stop is opened.
MAN mode AUT mode
RunTimer = 0
= disabled
RunTimer > 0
= enabled
RunTimer = 0
= disabled
RunTimer > 0
= enabled
Rem s/s = ON
Start and Run unlimited time
Rem s/s = OFF
No function
Cooling Cooling after
RunTimer is over
START
Engine runs
unlimited time
until STOP
Engine start-runs
Run.time and
then Cooling-
Stop
No function When Rem s/s =
OFF only:
Engine start-runs
Run.time and
then Cooling-
Stop
STOP
Cooling
No function when Rem s/s = 1
Cancels timer when Rem s/s = 0
2-nd STOP
Stop