ID–Lite-2.0 User guide, ©ComAp – January 2011 44
ID-Lite-2.0 User guide.pdf
Engines not started via CAN bus
PERKINS 2800 series
ID-Lite binary output description
Perkins Customer interface connector
Start output connects directly to engine starter solenoid
Fuel output 1,10,15,33,34
powers up ECU and enables the injectors
ID-Lite CAN description Perkins Customer interface connector
CAN bus common Screen for the J1939 cable.
CAN bus H 31
CAN bus L 32
JOHN DEERE
ID-Lite binary output description
John Deere 21 pin Deutsch connector
Start output D
Fuel output G (switched ECU power),J (ignition)
ID-Lite CAN description John Deere 21 pin Deutsch connector
CAN bus common Screen for the J1939 cable.
CAN bus H V
CAN bus L U
CUMMINS ISB/ISBE
ID-Lite binary output description
Cummins ISB OEM Harness connector B
Start output connects directly to engine starter solenoid
Fuel output 39
ID-Lite CAN description Cummins ISB 9 pin Deutsch connector
CAN bus common SAE J1939 shield - screen for J1939 cable.
CAN bus H SAE J1939 signal
CAN bus L SAE J1939 return