ID–Lite-2.0 User guide, ©ComAp – January 2011                                                   51 
ID-Lite-2.0 User guide.pdf 
Stopped engine conditions: RPM = 0, Engine params: Starting Poil, D+  (when enabled). 
Alarm  
The output closes if: 
• any warning or shutdown comes up or 
• the engine malfunctions 
The output opens if  
• FAULT RESET is pressed 
The output closes again if a new fault comes up. 
Horn 
The output closes if: 
• any warning or shutdown comes up or 
• the engine malfunctions 
The output opens if: 
• FAULT RESET is pressed or 
• HORN RESET is pressed or 
• Max time of HORN is exceeded (Horn timeout) 
The output closes again if a new fault comes up. 
 
Wrn AnImAIO1..4 
Output closes if the AIO: AI1..4 warning alarm activates. 
The output opens, if 
• alarm is not active and 
• FAULT RESET is pressed 
Sd AnImAIO1..4 
Output closes if the AIO: AI1..4 shutdown alarm activates. 
The output opens, if 
• alarm is not active and 
• FAULT RESET is pressed 
Ready 
The output is closed if following conditions are fulfilled: 
• Engine is not running and 
• No Shut down or Slow stop alarm is active 
• Controller is not in OFF mode 
Ready to load 
The output is closed if engine is running and no alarm is active - it is possible to close load. The output 
opens when Wrn underspeed protection is active and during cooling state. 
Running 
Output closes if the engine is in Running state. 
Cooling 
The output closes when engine is in Cooling state. 
Fault Reset 
One second pulse as echo for panel Fault reset button. 
Stop failed 
Output closes when the engine has to be stopped, but speed or oil pressure is detected. This 
protection goes active 60s after stop command.