InteliMains
NT
, SW version 3.2.0
InteliMains-NT-MCB-MGCB-3.2.0-Reference Guide.pdf, ©ComAp April 2015
364
See also the setpoint TimerChannel 4 and output TimerAct 1-4.
NOTE:
See the chapter Timers for more details about timers.
13.2.1.50 Binary input: Timer block 5
Related FW
standard v3.1.0
Description
This input is used to disable temporarily the output from the Timer channel
#5.
NOTE:
See also the setpoint TimerChannel 5 and output TimerAct 5-8.
NOTE:
See the chapter Timers for more details about timers.
13.2.1.51 Binary input: Timer block 6
Related FW
standard v3.1.0
Description
This input is used to disable temporarily the output from the Timer channel
#6.
NOTE:
See also the setpoint TimerChannel 6 and output TimerAct 5-8.
NOTE:
See the chapter Timers for more details about timers.
13.2.1.52 Binary input: Timer block 7
Related FW
standard v3.1.0
Description
This input is used to disable temporarily the output from the Timer channel
#7.
NOTE:
See also the setpoint TimerChannel 7 and output TimerAct 5-8.