InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp – July 2015
37
Output has no function. Use this configuration when output is not connected.
This output is dedicated for starter motor control. The number of cranking attempts is 6.
Prestart Time
0 - 600 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Maximum
Cranking Time
0 - 60 s
Cranging Fail
Pause 8 s
Gen-set start failed
On
Off
Start
Starter Output
Time
6 Cranking Attempts
Prestart Time Maximum
Cranking Time
0 - 60 s
Gen-set start failed – shutdown,
if the voltage or frequency are not in
the limit
On
Off
Time
Start
Engine run
Max. Stab. Time 7 sMin. Stab. Time
Starter Output
The starter output become inactive when one of following conditions is reach or exceeded.
RPM ≥ 25% of nominal RPM (1500RPM=50Hz; 1800RPM=60Hz)
or
Oil Pressure Analog ≥ 3 bar (43 PSI), only when Oil Pressure Starter Disengagement is enabled
or
Low Oil Pressure input is opened, only when Oil Pressure Starter Disengagement is enabled
or
voltage on D+ terminal ≥ 80% of battery voltage for 1 s or longer