InteliNano-NT Plus, SW version 2.0.1.x, ©ComAp July 2015
50
I20
Low Fuel Level
When this binary input is activated the red LED above Stop button will blink, the general warning
symbol will be displayed on LCD’s upper right corner, and Low Fuel Level symbol will be displayed
on event log with running hours stamp. This alarm is only warning. For more details see Warning
procedure in chapter 12 Alarm, Events and History Management.
NOTE:
Input has 10s delay.
I21
Fuel Level Analog
Analog input for fuel level measurement. When measured value exceeds the preset threshold, the left
red LED above Stop button will blink, the general warning symbol will be displayed on LCD’s upper
right corner, and fuel level symbol will be displayed on event log with running hours stamp. This alarm
is only warning. For more details see Warning procedure in chapter 12 Alarm, Events and History
Management.
Alarm threshold is 20% of measurement range. You can choose one from two preset resistive
sensors (VDO, Datcon) or you can create your own sensor curve.
NOTE:
Input has 10s delay.
VDO Level %
Ohm
%
1
0
0
2
10
0
3
96
50
4
180
100