6Mechanical Installation Installation & Commissioning Manual
28
5100607_CFD5000 T - CM2.2_Installation & Commissioning Manual_T_EN_2023_F
6.6.1.2 Mounting of UB-6 base plate
•
The detector base plate is mounted with two screws.
Figure 16. UB-6 base plate
Screw type: Depending on surface, maximum diameter of 4.2 mm / head max. 9 mm.
Tooling: Depending on screw type used.
Torque: Max 2.6 Nm.
6.6.1.3 Dismounting of UB-6 base plate
1. Disconnect the wires.
2. Unscrew the two screws holding the detector base, and remove base plate.
Screw type: N/A.
Tooling: Depending on screw type used.
Torque: +Max 2.6 Nm.
6.6.2 CS-PYH detector
6.6.2.1 General information
This section is intentionally left blank and may be replaced
by project specific product information.
6.6.2.2 Mounting of CS-PYH detector to base UB-6
1. Place the detector onto the base plate.