Installation & Commissioning Manual 9Safety validation and acceptance
5100607_CFD5000 T - CM2.2_Installation & Commissioning Manual_T_EN_2023_F
63
9 Safety validation and acceptance
NOTE!
Use Consilium document Acceptance Record for fire detection systems if nothing
else is agreed in project specific procedures.
Figure 36. An example from the document Acceptance Record
Perform the following steps as described in the Acceptance Record and document
the result of each test.
1. Visual inspections
2. Alarm tests
3. Fault tests
4. Input tests
5. Output tests
6. Other tests (where applicable)
7. Training (where applicable)
NOTE!
In order to be valid the Acceptance Record must be signed by the participant
representatives for the project.