10Fault codes Installation & Commissioning Manual
74
5100607_CFD5000 T - CM2.2_Installation & Commissioning Manual_T_EN_2023_F
Fault Code
Unit or
Module
Cause Remedy Failure classification
215
CHARGING
CURRENT
EXCEEDED
Charger M
The battery connected
to the affected Charger
M is charged with a
higher current than
allowed.
Charge the battery with an
external charger.
Major fault.
217
HIGH
VOLTAGE
PSU1
Charger M
The voltage delivered
from PSU 1 to the
affected Charger M
module is too high.
1. Measure the voltage
from the power source.
•
If voltage OK,
change module.
•
If voltage NOT OK,
change or adjust the
DC/DC acc. to data
sheet for the PSU.
2. Contact an authorised
service office.
Major fault.
CS-Loop M
CS-Safety M
CS-Com M
Voltage above 30
VDC in Backbone Bus
(BB) channel 1.
218
HIGH
VOLTAGE
PSU2
Charger M
The voltage delivered
from PSU 2 to the
affected Charger M
module is too high.
1. Measure the voltage
from the power source.
•
If voltage OK,
change module.
•
If voltage NOT OK,
change or adjust the
DC/DC acc. to data
sheet for the PSU.
2. Contact an authorised
service office.
•
Minor fault if power
sources are
redundant and not
from the same
source.
•
Major fault if power
from the same power
source.
CS-Loop M
CS-Safety M
CS-Com M
Voltage above 30
VDC in Backbone Bus
(BB) channel 2.
219
FUSE FAULT
PSU1
Charger M
The fuse protecting
the PSU 1 voltage
input is broken.
1. Check the fuse.
•
If fuse OK, change
module.
•
If fuse NOT OK,
change the fuse (or
change the module if
LRU).
2. Contact an authorised
service office.
•
Minor fault if power
sources are
redundant and not
from the same
source.
•
Major fault if power
from the same power
source.
220
FUSE FAULT
PSU2
Charger M
The fuse protecting
the PSU 2 voltage
input is broken.
1. Check the fuse.
•
If fuse OK, change
module.
•
If fuse NOT OK,
change the fuse (or
change the module if
LRU).
2. Contact an authorised
service office.
•
Minor fault if power
sources are
redundant and not
from the same
source.
•
Major fault if power
from the same power
source.