- 37 -
value starts from a user home position.
If the stroke limit is exceeded
If one of stroke limits is exceeded, a controller turns off READY and will be in
a servo off state. Please input RESET, in order to restore. If ON of READY is
checked, please move ram into a stroke limit by manual operation.
A motion of the ram at the time of servo off
At the moment of servo-off, a ram may shift from various factors slightly. The
amount of shift is 1mm or less. In order to prevent the shift, please stop
servo-off or use the brake for position keeping.
*1 A tool table is the file various setting value about a tool is indicated to be. It
exists under the installation folder of BS Configurator. If a tool type is chosen
on a tool selection screen, the contents of a tool table will be displayed.