Keypad/dIsplay Menu structure
The following is a description of the MicroTech III menu structure. These menus and items can all be displayed with the keypad/
display. Menu items displayed will change based on the selected unit conguration.
Figure 7: Main Menu – Keypad/Display Menu Structure
For more detail go to:
Figure 8, page 12
For more detail go to:
Figure 10, page 18
For more detail go to:
Figure 11, page 22
Main Menu
Enter Password
Quick Menu
View/Set Unit
Unit State=_________
Unit Status=________
MWU Status=
Dehum Status=
Ctrl Mode= Off
Occ Mode= Auto
HP Mode=
Commission Unit
Manual Control
Service Menus
Trending
Unit Maintenance
BMS Communications
Unit Conguration
Alarm Lists
About This Unit
See page 23 — 24
Quick Menu
Unit State=__________ DAT Clg Spt= 55.0°F
Unit Status=_________ DAT Htg Spt= 85.0°F
MWU Status=_________ Min DAT Limit= 55.0°F
Dehum Status=________ Unocc Clg Spt= 85.0°F
Ctrl Mode= Off Unocc Htg Spt= 55.0°F
Occ Mode= Auto/Net SAF Speed= XXX%
HP Mode= Auto Duct Press= X.Xin
Clg Capacity= XXX% DuctSP Spt= 1.0in
OAD/Econ Cap= XXX% RF/EF Cap= XXX%
Htg Capacity= XXX% Bldg Press= X.XXin
Supl Htg Cap= XXX% BldgSP Spt= 0.05in
Reheat Cap= XXX% IAQ PPM= XXXXppm
Control Temp= XXX% OA Flw= XXXXXCFM
Occ Clg Spt= 72.0°F MinOAFlw Spt= 2000CFM
Occ Htg Spt= 68.0°F OA Temp= XXX°F
Disch Air= XXX°F EW Temp= XXX°F
Rel Humidity= XXX%
See page 72
About This Unit
SO_Item= 123456_12345
Unit SN= FBOU123456789
App Version= 2506017xxx
Cf1-15= xxxxxxxxxxxxxxxx
Cf6-29= xxxxxxxxxxxxxxxx
Main BSP= X.XX
LON BSP= X.XX
LON App Ver= X.XX
BACnet BSP= X.XX
D-Net BSP= X.XX
HMI GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
OBH GUID=
xxxxxxxx-xxxx-xxxx-xxxx-
xxxxxxxxxxxx
See page 25 — 33
View/Set Unit
Unit Status/Settings
Occupancy
Temperatures
Flow Status
SAF Spd Control
RF/EF Control
Cooling
Economizer
Min OA Damper
Heating
Dehumidication
Date/Time/Schedules
See page 7
Enter Password
Enter Password *******
See page 68
BMS Communications
LON Set-Up
BACnet MSTP Set-Up
BACnet IP Set-Up
D-Net Set-Up
Network Unit Set-Up
Comm Slot 1= 0
Comm Slot 2= 0
Comm Slot 3= 0
See page 69
Unit Conguration
Apply Changes= No
Unit Type= RTU(0)
Control Type= DAT(1)
Clg Type= Comp(1)
Comp Cong= 424(1)
Gen Clg Stgs=/VFDCmpCFG= 8
Low Ambient= No(0)
Cond Ctrl= Std2(0)
OA Dmpr/Econ= AirEc(3)
OA Flow Stn= None(0)
Htg Type= None(0)
Htg Stages= 1
Max Heat Rise= 100
SAF Type= CAV(0)
RAF Type= CAV(0)
RF/EF Ctrl= Track(1)
2ndDSPSnsr= No(0)
EFT/LCT Snsr= No(0)
Energy Rcvy= None(0)
Clg Circ Type= 2Air(2)
Head P Ctrl= No(0)
Bypass Ctrl= Slave(0)
Unit Size= 050
Refrig Type= R410A(2)
Reheat Type= None(0)
Unit Voltage= 460/60(2)
EV Type= EVBSag
Apply Changes= No
See page 63
Alarm Lists
Active Alarms
Alarm Log
OM 1141-3 • MICROTECH UNIT CONTROLLER 10 www.DaikinApplied.com