Min OA Set-Up Menu
(See page 104 for more information)
Table 28: Min OA Damper Menu
Item Display
Name
Default
Setting
Range
Password
Level
Item Display
Name
Default
Setting
Range
Password
Level
AplyMinOAChg= No No, Yes 4 CFM Reset
Min OA Reset= None
None
4
OA Flow= — 0–60000CFM 4
Network MinOAFlw Spt= 2000CFM 0–60000CFM 4
Ext VDC
Field Stn Rst= No
No
4
Ext mA Yes
IAQ VDC
Field Stn Cfg= VDC
VDC
4
IAQ mA mA
BSPOAOvrd= No No, Yes 2 Min CFM 0CFM 0-60000CFM 4
RstLmtSnsr= None
None
2
Max CFM 10000CFM 0-60000CFM 4
DAT
V/A @Min CFM= 0.0/V
0.0-20.0/
4EFT V
MAT mA
External Reset
V/A @Max CFM= 10.0/V
0.0-20.0/
4OA @ MinV/mA= 0% 0-100% 4 V
OA @ MaxV/mA= 100% 0-100% 4 mA
Min V/mA= 0.0/V
0.0-20.0/
4
OA CFM DB= 3% 0–100% 4
V OA CFM Period= 30s 0–999s 4
mA OA CFM Gain= 0.1 0.0–100.0 4
Max V/mA= 10.0/V
0.0-20.0/
4
OA CFM Mx
Chg=
5% 0–100% 4
V Fan Speed Reset
mA Min Clg Spd= 40% 0-100% 4
CO
2
Reset Des Clg Spd 100% 0-100% 4
IAQ Reset= Yes
No
4
BSP Reset
Yes MinRFEFTm= 120sec 0-3600sec 2
PPM @DCV Lmt= 800ppm 0-5000ppm 4 BSPOvdST= 5Sec 0-999Sec 2
PPM @Vnt Lmt= 1000ppm 0-5000ppm 4 BSPOvdGain= 0.2 0-999 2
IAQ PPM= — 0-5000ppm 4 BSPOvdMxChg= 4% 0-100% 2
Min PPM= 0ppm 0-5000ppm 4 Damper Limiting
Max PPM= 2000ppm 0-5000ppm 4 ResetTLmt= 32.0°F 0-100°F 2
V/A @Min PPM= 0.0/V
0.0-20.0/
4
RstTSmplT= 5Sec 0-999Sec 2
V RstTGain= 0.2 0-999 2
mA RstTPAT= 60Sec 0-999Sec 2
V/A @Max PPM= 10.0/V
0.0-20.0/
4
RstTMaxChg= 4% 0-100% 2
V 0-30% OA Max= 30% 0-100% 2
mA Min Inc Rate= 0.03 0.0-100.0 2
Max Inc Rate= 1.0 0.0-100.0 2
OM 1141-3 • MICROTECH UNIT CONTROLLER 46 www.DaikinApplied.com
coMMIssIon unIt