Daikin DPS - ERROR CODE: L5 - Momentary Overcurrent of Inverter Compressor

Daikin DPS
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ERROR CODE: L5 – Momentary Overcurrent of Inverter Compressor
Remote
Controller
Display
L5
Method of
Malfunction
Detection
Malfunction is detected from current owing in the power transistor.
Malfunction
Decision
Condition
When an excessive current ows in the power transistor.
(Instantaneous overcurrent also causes activation.)
Supposed
Causes
Defect of compressor coil (disconnected, defective insulation)
Compressor start-up malfunction (mechanical lock)
Defect of inverter PC board