ERROR CODE: U2 – Power Supply Insufcient or Instantaneous Failure
Remote
Controller
Display
U2
Method of
Malfunction
Detection
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Decision
Condition
When the voltage aforementioned is not less than 780V or not more than 320V, or when
the current-limiting voltage does not reach 200V or more or exceeds 740V.
For 230V units: When the voltage aforementioned is not more than 190V.
Supposed
Causes
Power supply insufcient
Instantaneous power failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect
Faulty compressor
Faulty fan motor
Faulty connection of signal cable