EasyManua.ls Logo

Daikin DPS - ERROR CODE: L4 - Malfunction of Inverter Radiating Fin Temperature Rise

Daikin DPS
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ERROR CODE: L4 – Malfunction of Inverter Radiating Fin Temperature Rise
Remote
Controller
Display
L4
Method of
Malfunction
Detection
Fin temperature is detected by the thermistor of the radiation n.
Malfunction
Decision
Condition
When the temperature of the inverter radiation n increases above 188.6°F.
Supposed
Causes
Actuation of n thermal (Actuates above 188.6°F)
Defect of inverter PC board
Defect of n thermistor
trouBleshootIng
www.DaikinApplied.com 137 OM 1141-3 • MICROTECH UNIT CONTROLLER