Inverter Compressor Set-Up
(See page 87 — 90 for more information)
Table 26: Inverter Compressor Set Up Menu
Item
Display Name
Default
Setting
Range Password Level
Compressor Status
Clg State= —
Off
4
Start
Init
Normal
Pumpdn
Standby
Htg State= —
Off
4
Start
Init
Normal
Pumpdn
Standby
INV Cmp Spd= — 0–100% 4
INV Spd Cmd= — 0–100% 4
Comp 3 —
Off
4
On
Prev Standby= —
None
2
CHP
HLP
CLP
HHP
INVDLT
LoDP
OAFail
OAFReq
INVReq
CmpDsbl
INV Port Temp= — -50.0–200.0°F 2
INV Fin Temp= — -50.0–200.0°F 2
INV Cmp Amps= — 0–50A 2
Refrig Circuit Status
PTD= — 0–5000kPa 4
PTS= — 0–5000kPa 4
4 WayValve= —
Cool
2
Heat
RcvrSol Valve= —
Closed
2
Open
BP Sol Valve= —
Closed
2
Open
Compressor Set Up
Clg Lo OAT Lk= 25°F 0–100°F 4
Htg Lo OAT Lk= 0°F -20–50°F 4
Htg Hi OAT Lk= 55°F 0–100°F 4
Eff Htg Hi OAT Lk= — 0–100°F 4
OAT Diff= 2°F 0–100°F 4
INV Period= 20s 0–999s 4
INV Gain= 2.5 0.0–100.0 4
INV PAT= 10s 0–999s 4
INV Max Chg= 15% 0–100% 4
Item
Display Name
Default Setting Range Password Level
Compressor Limiting
Clg Press Lmtg= —
None
2
LP
LDP
HP
LPLDP
HPLDP
LDHP
Htg Press Lmtg= —
None
2
LP
HP
HPP
LPHP
LPHPP
HPHPP
LPHPHPP
C Ratio Lmtg —
None
2
Active
Ref DLT Lmtg —
None
2
INV
STD
INVSTD
INV Brd Lmtg= —
None
2
HiA
Req
FinT
HiAReq
HiAFinT
ReqFinT
HiARqFT
INV Man Dsbl= Enable
Enable
2
Disable
Comp3 ManDsbl= STD2ManOff
Enable
2
Disable
Fault Code Details (Active Fault Codes)
INVAlarmCode= — 2 digit alpha-numeric 2
Code Text — String 2
OF1AlarmCode= — 2 digit alpha-numeric 2
Code Text — String 2
OF2AarmCode= — 2 digit alpha-numeric 2
Code Text — String 2
Fault Code Details (Previous Fault Codes)
PrvINVAlmCode= — 2 digit alpha-numeric 2
Code Text — String 2
MM/DD/YY HH:MM:SS — — 2
PrvOF1 Alm Code= — 2 digit alpha-numeric 2
Code Text — String 2
MM/DD/YY HH:MM:SS — — 2
PrvOF2AlmCode= — 2 digit alpha-numeric 2
Code Text — String 2
MM/DD/YY HH:MM:SS — — 2
IFB Communication Status
IFB SWVersion= — V022013 2
IFBCommStatus=
See page 123
—
OK
2
OF2Err
OF1Err
OF12Err
INVErr
ACS3Err
ACS1Err
ACS13Err
Init3Err
Init1Err
Init13Err
MBErr
PrvCommStatus —
Same as IFB Com-
mStatus
2
MM/DD/YY HH:MM:SS — — 2
ACS1 DataRcvd=
See page 124
—
ErrAll
2
F1F2Err
INVF2Err
F2Err
INVF1Err
F1Err
INVErr
AllOK
ACS3 DataRcvd=
See page 124
—
Error
2
OK
OM 1141-3 • MICROTECH UNIT CONTROLLER 42 www.DaikinApplied.com