Daikin DPS - ERROR CODE: P4 - Malfunction of Inverter Radiating Fin Temperature Rise Sensor

Daikin DPS
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ERROR CODE: P4 – Malfunction of Inverter Radiating Fin Temperature Rise Sensor
Remote
Controller
Display
P4
Method of
Malfunction
Detection
Resistance of radiation n thermistor is detected when the compressor is not operating.
P4” will be displayed by pressing the inspection button.
Supposed
Causes
Defect of radiator n temperature sensor
Defect of inverter PC board
Faulty inverter compressor
Faulty fan motor