BMs coMMunIcatIon
LON/BACnetIP/BACnetMSTP Setup Menu
See the Installation & Maintenance Manuals for detailed instructions
IM 916–MicroTech III Rooftop unit controller - BACnet IP
communications
IM 917–MicroTech III Rooftop unit controller - BACnet
MSTP communications
IM 918–MicroTech III Rooftop unit controller - Lon
communications
Network Unit Set-up Menu
The Network Unit Set-up menu provides one location for the Set-up of items that can be controlled via a network BMS system.
Table 52: Network Unit Set-up Menu
Item Display Name
Default
Setting
Range
Password
Level
Item Display Name
Default
Setting
Range
Password
Level
Space Sensor= Digtl/Net
None
2
Heat/Cool Changeover
Anlog/Net
Ctrl Temp Src= RAT
RAT
2
Digtl/Net Space
Unit Mode Settings MAT
Ctrl Mode= Off
Off
2
OAT
Heat Only None
Cool Only
AplyTstatChg= No
No
2
Fan Only Yes
Heat/Cool
UseTstatSpt= No
No
2
Auto/Net Yes
Occ Mode= Auto/Net
Occ
2
Oc c Clg Spt= 72.0°F 0.0-100.0°F 2
Unocc Occ Htg Spt= 68.0°F 0.0-100.0°F 2
TntOvrd Fan Control Options
Auto/Net
SAF Ctrl= DSP
DSP
2
Reset Options Spd/Net
Clg Reset= None
None
2
1ZnVAV
Network BPS
Space CO
2
Return CFM
OAT
RFEF BldgP
None
2
ExtmA Tracking
ExtV BldgP
Airow Spd/Net
Htg Reset= None
None
2
OA Damper
Network
Space
Return
OAT
ExtmA
ExtV
Airow
AplyMinOAChg= No No, Yes 2
Min OA Reset= None
None
2
Network
Ext VDC
Ext mA
IAQ VDC
IAQ mA
OM 1141-3 • MICROTECH UNIT CONTROLLER 68 www.DaikinApplied.com