serVIce Menus
Timer Settings Menu
The Timer Settings Menu is also available from the
Commission Unit Menu, and is described on page 34.
Save/Restore Menu
The Save/Restore menu can be used to save or restore the
user congured parameters as well as reset the controller back
to the factory default parameters.
Table 40: Save/Restore Menu
Save Params is an adjustable item used to save the current
parameters and conguration.
Rstr Params is an adjustable item used to restore the current
parameters and conguration.
Rstr Factory is an adjustable item used to restore the factory
parameters and conguration.
SaveToCard is an adjustable item used to save the current
parameters and conguration to an SD card.
LoadFromCard is an adjustable item used to restore the
current parameters and conguration from an SD card.
NOTE: The controller will automatically perform a reset when
the value of Load From Card is changed from No to
Yes and the enter button is pushed.
Operating Hours
The Operating Hours menu gives a summary of the hours of
operation for each of the supply fans, return/exhaust fans,
compressors, heating and economizer operation.
Table 41: Operating Hours Menu
Supply Fan is a status item which gives the number of hours
the supply fan has operated.
Return/Exhaust Fan is a status item which gives the number
of hours the return/exhaust fans have operated.
Cmp Cooling is a status item which indicates the number of
hours compressor cooling has operated.
INV Comp is a status item which indicates the number of hours
the inverter compressor has operated.
Comp 3 is a status item which indicates the number of hours
the xed speed compressor has operated.
Heating is a status item which gives the number of hours that
the heating mode has operated.
Cmp Heating is a status item which indicates the number of
hours compressor heating has operated.
Economizer is a status item which gives the number of hours
that the economizer has operated.
Tnt Override is a status item which gives the number of hours
that the unit has operated in the Tenant Override mode of
operation.
Dehumid is a status item which gives the number of hours that
the dehumidication has operated.
ER Wheel is a status item which gives the number of hours
that the energy recovery wheel has operated.
Reheat is a status item which gives the number of hours the
reheat has operated.
Item Display
Name
Default
Setting
Range
Password
Level
Save Params= No No/Yes 2
Rstr Params= No No/Yes 2
Rstr Factory= No No/Yes 2
SaveToCard= No No/Yes 2
LoadFromCard No No/Yes 2
Item Display
Name
Default
Setting
Range
Password
Level
Supply Fan= 0–50000H 6
Ret/Exh Fan= 0–50000H 6
Cmp Cooling= 0–50000H 6
INV Comp= 0–50000H 6
Comp3= 0–50000H 6
Heating= 0–50000H 6
Cmp Heating= 0–50000H 6
Economizer= 0–50000H 6
Tnt Override= 0–50000H 6
Dehumid= 0–50000H 6
ER Wheel= 0–50000H 6
Reheat= 0–50000H 6
OM 1141-3 • MICROTECH UNIT CONTROLLER 62 www.DaikinApplied.com