serVIce Menus
Timer Settings Menu
The Timer Settings Menu is also available from the
Commission Unit Menu, and is described on page 34.
Save/Restore Menu
The Save/Restore menu can be used to save or restore the
user congured parameters as well as reset the controller back
to the factory default parameters.
Table 40: Save/Restore Menu
Save Params is an adjustable item used to save the current
parameters and conguration.
Rstr Params is an adjustable item used to restore the current
parameters and conguration.
Rstr Factory is an adjustable item used to restore the factory
parameters and conguration.
SaveToCard is an adjustable item used to save the current
parameters and conguration to an SD card.
LoadFromCard is an adjustable item used to restore the
current parameters and conguration from an SD card.
NOTE: The controller will automatically perform a reset when
the value of Load From Card is changed from No to
Yes and the enter button is pushed.
Operating Hours
The Operating Hours menu gives a summary of the hours of
operation for each of the supply fans, return/exhaust fans,
compressors, heating and economizer operation.
Table 41: Operating Hours Menu
Supply Fan is a status item which gives the number of hours
the supply fan has operated.
Return/Exhaust Fan is a status item which gives the number
of hours the return/exhaust fans have operated.
Cmp Cooling is a status item which indicates the number of
hours compressor cooling has operated.
INV Comp is a status item which indicates the number of hours
the inverter compressor has operated.
Comp 3 is a status item which indicates the number of hours
the xed speed compressor has operated.
Heating is a status item which gives the number of hours that
the heating mode has operated.
Cmp Heating is a status item which indicates the number of
hours compressor heating has operated.
Economizer is a status item which gives the number of hours
that the economizer has operated.
Tnt Override is a status item which gives the number of hours
that the unit has operated in the Tenant Override mode of
operation.
Dehumid is a status item which gives the number of hours that
the dehumidication has operated.
ER Wheel is a status item which gives the number of hours
that the energy recovery wheel has operated.
Reheat is a status item which gives the number of hours the
reheat has operated.
Item Display
Name
Default
Setting
Range
Password
Level
Save Params= No No/Yes 2
Rstr Params= No No/Yes 2
Rstr Factory= No No/Yes 2
SaveToCard= No No/Yes 2
LoadFromCard No No/Yes 2
Item Display
Name
Default
Setting
Range
Password
Level
Supply Fan= — 0–50000H 6
Ret/Exh Fan= — 0–50000H 6
Cmp Cooling= — 0–50000H 6
INV Comp= — 0–50000H 6
Comp3= — 0–50000H 6
Heating= — 0–50000H 6
Cmp Heating= — 0–50000H 6
Economizer= — 0–50000H 6
Tnt Override= — 0–50000H 6
Dehumid= — 0–50000H 6
ER Wheel= — 0–50000H 6
Reheat= — 0–50000H 6
OM 1141-3 • MICROTECH UNIT CONTROLLER 62 www.DaikinApplied.com
serVIce Menus