RF/EF Spd Cmd is an adjustable item for units with variable
speed supply air fan on the return/exhaust fans that sets the
speed of the return/exhaust fan.
OAD/Econo is an adjustable item which is used to set the
economizer damper position.
GasHtgOnOff is an adjustable item used to turn the gas heat
enable output On and Off.
Htg Valve is an adjustable item used to manually drive the
modulating heating valve open and closed.
SCR Out is an adjustable item used to manually drive the
output signal to the SCR.
Htg Stg 1 is an adjustable item that turns on the rst stage of
heat on units equipped with staged heating.
SCR Ena 1 is an adjustable item that enables the SCR heater.
Htg Stg 2 is an adjustable item that turns on the second stage
of heat on units equipped with staged heating.
Htg Stg 3 is an adjustable item that turns on the third stage of
heat on units equipped with staged heating.
Htg Stg 4 is an adjustable item that turns on the fourth stage of
heat on units equipped with staged heating.
Reheat Valve is an adjustable item used to manually drive the
reheat valve open and closed.
ERec Wheel is an adjustable item which is used to turn on/off
the energy recovery wheel output.
ERec Whl Cmd is an adjustable item is an adjustable item
which is used to set the energy recovery wheel variable speed
supply air fan speed.
ERBP Dmpr Cl is an adjustable item which is used to close the
energy recovery bypass damper.
ERBP Dmpr OP is an adjustable item which is used to open
the energy recovery bypass damper.
Alm Output is an adjustable item which is used to turn on/off
the alarm output.
FanOp is an adjustable item which is used to turn on/off the
fan operation output.
When Manual Control is set to ManCtrl, the Control Mode is
set to Off so that the unit will not restart automatically. When
Manual Control is set to Normal all digital outputs in the Manual
Control menu are set to Off and all the analog outputs are set
to 0.0% so that all outputs are in the Off or minimum position
when Manual Control is set to ManCtrl
Manual control Menu
www.DaikinApplied.com 61 OM 1141-3 • MICROTECH UNIT CONTROLLER