PHA = Phase failure
UzLow = DC-Link Undervoltage
UzHigh = DC-Link Overvoltage
UeHigh = Mains Overvoltage
UeLow = Mains Undervoltage
Question: • Can the main voltage be measured at any spot; a data logger may be helpful.
No: Measure the voltage at the power supply input of the concerned fan.
Corrective: • Reset the failure; re-start the motor and observe it.
• If applicable, lter out the source of disturbing signal.
Repeated occurrence:
Question: • Do other fans show the same failure?
• How often does the failure occur?
• Get big electrical consumer loads switched at the same time when the failure occurs in the surrounding area?
Are compressors or large asynchronous motors applied within the arrangement?
Yes: Systematic search for external disturbance voltage peaks; If applicable, usage of data logger for a longer
period and analysis of the measured values.
Are the voltage values within the specied range?
No: It seems to be a hardware problem of the fan. Fan need to be replaced.
OM 1141-3 • MICROTECH UNIT CONTROLLER 156 www.DaikinApplied.com