29-21 Derag Power[HP]
Range: Function:
0 hp* [0 - 0 hp] Readout of calculated derag power at actual
speed.
29-22 Derag Power Factor
Range: Function:
200 %* [1 - 400 %] Set a correction if derag detection reacts
on too low a power value.
29-23 Derag Power Delay
Range: Function:
601 s* [1 - 601 s] The time that the frequency converter must
remain on reference and a high-power
condition for a derag to occur.
29-24 Low Speed [RPM]
Range: Function:
Size related* [ 0 - par. 29-28
RPM]
Set output speed used for
registration of derag power at
low speed in RPM.
29-25 Low Speed [Hz]
Range: Function:
Size related* [ 0 - par. 29-29
Hz]
Set output speed used for
registration of derag power at
low speed in Hz.
29-26 Low Speed Power [kW]
Range: Function:
Size related* [ 0 - 5.50 kW] Set derag power at low speed in
kW.
29-27 Low Speed Power [HP]
Range: Function:
Size related* [ 0 - 7.50 hp] Set derag power at low speed in
hp.
29-28 High Speed [RPM]
Range: Function:
Size related* [ 0.0 - par. 4-13
RPM]
Set output speed used for
registration of derag power at
high speed in RPM.
29-29 High Speed [Hz]
Range: Function:
Size related* [ 0.0 - par.
4-14 Hz]
Set output speed used for
registration of derag power at
high speed in Hz.
29-30 High Speed Power [kW]
Range: Function:
Size related* [ 0 - 5.50 kW] Set derag power at high speed in
kW.
29-31 High Speed Power [HP]
Range: Function:
Size related* [ 0 - 7.50 hp] Set derag power at high speed in
hp.
29-32 Derag On Ref Bandwidth
Range: Function:
5 %* [1 - 100 %] Set the bandwidth percentage of motor
speed high limit to accommodate system
pressure uctuation.
29-33 Power Derag Limit
Range: Function:
3* [0 - 10 ] The number of times the power monitor can
trigger consecutive derags before a fault is
reported.
29-34 Consecutive Derag Interval
Range: Function:
Size related* [Size related] Derags are considered to be
consecutive if they happen within
the interval specied in this
parameter.
Parameter Description
VLT
®
AQUA Drive FC 202
238 Danfoss A/S © 05/2018 All rights reserved. MG20OB02
33

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT AQUA Drive FC 202 and is the answer not in the manual?

Danfoss VLT AQUA Drive FC 202 Specifications

General IconGeneral
BrandDanfoss
ModelVLT AQUA Drive FC 202
CategoryDC Drives
LanguageEnglish

Related product manuals