EasyManua.ls Logo

Danfoss VLT AQUA Drive FC 202

Danfoss VLT AQUA Drive FC 202
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
O delay timer=10 s. The nominal power must be
below 10% for 10 s to disconnect the capacitors.
If the nominal power exceeds 10% during the 10
s delay, the timer (10 s) restarts.
The capacitor reconnect delay (default=25 s with
a range 1–120 s, see parameter 5-80 AHF Cap
Reconnect Delay) is used for the minimum o-
time for the AHF capacitor output function.
If there is a power loss, the frequency converter
guarantees that the minimum o-time is
respected when power is restored.
10 20 30 40 50 60 70 80 90 100 110 120 130
Time (s)
Relay Output
On
t
1
t
2
130BC368.10
Nominal Power of Drive
0%
10%
20%
30%
40%
50%
60%
70%
80%
90%
100%
...................................................................................................................................................................................................................
....................................................................................................................................................................................................................
....................................................................................................................................................................................................................
Illustration 3.33 Example of the Output Function
t
1
shows the o delay timer (10 s).
t
2
shows the capacitor reconnect delay (parameter 5-80 AHF
Cap Reconnect Delay).
When the nominal power of the frequency converter
exceeds 20%, the output function turns on. When the
power goes below 10%, an o delay timer has to expire
before the output goes low. This is represented by t
1
. After
the output goes low, the capacitor reconnect delay timer
has to expire before the output is allowed to be on again,
shown by t
2
. When t
2
expires, the nominal power is above
30% and the relay does not turn on.
3.7.7 5-9* Bus-controlled
This parameter group selects digital and relay outputs via a
eldbus setting.
5-90 Digital & Relay Bus Control
Range: Function:
0* [0 -
2147483647 ]
This parameter holds the state of the digital
outputs and relays that are controlled by
bus.
A logical 1 indicates that the output is high
or active.
A logical 0 indicates that the output is low
or inactive.
Bit 0 CC digital output, terminal 27
Bit 1 CC digital output, terminal 29
Bit 2 GPIO digital output, terminal X
30/6
Bit 3 GPIO digital output, terminal X
30/7
Bit 4 CC relay 1 output terminal
Bit 5 CC relay 2 output terminal
Bit 6 Option B relay 1 output terminal
Bit 7 Option B relay 2 output terminal
Bit 8 Option B relay 3 output terminal
Bit 9–
15
Reserved for future terminals
Bit 16 Option C relay 1 output terminal
Bit 17 Option C relay 2 output terminal
Bit 18 Option C relay 3 output terminal
Bit 19 Option C relay 4 output terminal
Bit 20 Option C relay 5 output terminal
Bit 21 Option C relay 6 output terminal
Bit 22 Option C relay 7 output terminal
Bit 23 Option C relay 8 output terminal
Bit 24–
31
Reserved for future terminals
Table 3.16 Digital Output Bits
5-93 Pulse Out #27 Bus Control
Range: Function:
0 %* [0 - 100 %] Contains the frequency to apply to the
digital output terminal 27 when it is
congured as bus-controlled.
5-94 Pulse Out #27 Timeout Preset
Range: Function:
0 %* [0 - 100 %] Contains the frequency to apply to the
digital output terminal 27 when it is
congured as bus-controlled timeout, and
timeout is detected.
5-95 Pulse Out #29 Bus Control
Range: Function:
0 %* [0 - 100 %] Contains the frequency to apply to the
digital output terminal 29 when it is
congured as bus-controlled.
Parameter Description Programming Guide
MG20OB02 Danfoss A/S © 05/2018 All rights reserved. 89
3 3

Table of Contents

Other manuals for Danfoss VLT AQUA Drive FC 202

Related product manuals