GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 106 of 123
4620 VDO fuel level input 1.3
No. Setting Min. setting Max. setting Factory
setting
4621 Fuel level 1.3 (P3) Set point 0 % 100 % 80 %
4622 Fuel level 1.3 (P3) Delay 0.0 s 100.0 s 5.0 s
4623 Fuel level 1.3 Output A R0 (none) R26 (relay 26) R0 (none)
4624 Fuel level 1.3 Output B R0 (none) R26 (relay 26) R0 (none)
4625 Fuel level 1.3 Enable OFF ON OFF
4626 Fuel level 1.3 Fail class See description of fail classes
4950 Battery low 2
No. Setting Min. setting Max. setting Factory
setting
4951 Battery low 2 Set point 6.0V 36.0V 15.0V
4952 Battery low 2 Timer 0.0 s 999.0 s 1.0 s
4953 Battery low 2 Relay output A R0 (none) R26 (relay 26) R0 (none)
4954 Battery low 2 Relay output B R0 (none) R26 (relay 26) R0 (none)
4955 Battery low 2 Enable OFF ON ON
4960 Battery low 1
No. Setting Min. setting Max. setting Factory
setting
4961 Battery low V* Set point 6.0V 36.0V 18.0V
4962 Battery low V* Timer 0.0 s 999.0 s 1.0 s
4963 Battery low V Relay output A R0 (none) R26 (relay 26) R0 (none)
4964 Battery low V Relay output B R0 (none) R26 (relay 26) R0 (none)
4965 Battery low V Enable OFF ON ON
4970 Battery high voltage
No. Setting Min. setting Max. setting Factory
setting
4971 Battery high V* Set point 12.0V 40.0V 28.0V
4972 Battery high V* Timer 0.0 s 10.0 s 1.0 s
4973 Battery high V Relay output A R0 (none) R26 (relay 26) R0 (none)
4974 Battery high V Relay output B R0 (none) R26 (relay 26) R0 (none)
4975 Battery high V Enable OFF ON OFF
5000...5060 Relay functions
No. Setting First/min.
setting
Second/max.
setting
Factory
setting
50X1 Relay X Function Alarm Limit Alarm
50X2 Relay X Off delay 0.0 s 999.9 s 5.0 s
5110 Relay function
No. Setting First/min.
setting
Second/max.
setting
Factory
setting
5111 Relay 3 Function Alarm Limit Alarm
5112 Relay 3 Off delay 0.0 s 999.9 s 5.0 s
If option B3 is present, then parameters 5050 and 5060 are not available.
Relay 3 can be used for “Status Ok” or as configurable relay. Only HW 1.05.