GC-1F Installation Instructions and Reference Handbook
DEIF A/S Page 58 of 123
The PC utility software setting looks like this:
VDO input 3, cooling water temperature
VDO sensor
type
Temperature Type 1 Type 2 Type 3 Type 4 Type 5
°C °F
40 104 291.5 480.7 69.3 952 Configurable
50 122 622
60 140 134.0 222.5 36.0 426
70 158 97.1 27.9 290
80 176 70.1 113.2 19.8 197
90 184 51.2 83.2 15.8 147
100 212 38.5 62.4 11.7 106
110 230 29.1 47.6 9.5 90
120 248 22.4 7.4 76
130 266 28.9 65
140 284 55
150 302 18.2 46
Eight settings are available from 0 to 10 bar.
Type 4 is fully configurable with eight points in the range 0 to 2500 and 40 to
150 °C or 104 to 302 °F.