連接至AC之電壓必須符合下列規範:
三相三線: 三相四線:
L1-L2: 400 Vac ± 20% L1-N: 230 Vac ± 20%
L1-L3: 400 Vac ± 20% L2-N: 230 Vac ± 20%
L2-L3: 400 Vac ± 20% L3-N: 230 Vac ± 20%
AC配線完成後使用者須於控制面板上選擇相對應的AC接線方式,以確保機子能正確
判讀電壓。設定方式請參考5.2.7 Install Settings。
不建議N與PE壓差>20Vrms 的TT接地系統。
接地系統 TN-S
是否允許 Yes
TN-C
Yes
TN-C-S
Yes
TT
Yes
IT
No
4.2.2 允許接地系統