Message Possible cause Action
7 Error message and Trouble Shooting
AC Freq
High
(E01)
1. Actual utility frequency is over
    the OFR setting
2. Incorrect country setting
3. Detection circuit malfunction
1. Check the utility frequency on the
    inverter terminal
2. Check country setting
3. Check the detection circuit inside the
    inverter
AC Freq
Low
(E02)
1. Actual utility frequency is under
    the UFR setting
2. Incorrect country or Grid setting
3. Detection circuit malfunction
1. Check the utility frequency on the
    inverter terminal
2. Check country & Grid setting
3. Check the detection circuit inside the
    inverter
Grid Quality
(E07)
Non-linear load in Grid and near
to inverter
Grid connection of inverter need to be
far away from non-linear load if necessary
HW Con.
Fail
(E08)
1. Wrong connection in AC plug
2. Detection circuit malfunction
1. Check the AC connection, must accords
    to manual
2. Check the detection circuit inside the
    inverter
No Grid
(E09)
1. AC breaker is OFF
2. Disconnect in AC plug
1. Switch on AC breaker
2. Check the connection in AC plug and
    make sure it connects to inverter
AC Volt
Low
(E10, E15,
E20)
1. Actual utility voltage is under
 the UVR setting
2. Incorrect country or Grid setting
3. Wrong connections in AC plug
4. Detection circuit malfunction
1. Check the utility voltage connection
    to the inverter terminal
2. Check country & Grid setting
3. Check the connection in AC plug
4. Check the detection circuit inside the
    inverter
AC Volt
High
(E11, E13,
E16, E18,
E21, E23)
1. Actual utility voltage is over the
    OVR setting
2. Utility voltage is over the Slow
    OVR setting during operation
3. Incorrect country or Grid setting
4. Detection circuit malfunction
1. Check the utility voltage on the inverter
    terminal
2. Check the utility voltage on the inverter
    terminal
3. Check country & Grid setting
4. Check the detection circuit inside the
    inverter
Solar1
High
(E30)
1. Actual Solar1 voltage is over
    1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
    make the Voc less than 1000Vdc
2. Check the detection circuit inside the
    inverter
EPO
(E25)
1. EPO is activated by user
2. Detection circuit malfunction
1. Release the EPO button
2. Check the detection circuit inside the
    inverter
Solar2
High
(E31) 
1. Actual Solar2 voltage is over
    1000Vdc
2. Detection circuit malfunction
1. Modify the solar array setting, and
    make the Voc less than 1000Vdc
2. Check the detection circuit inside the
    inverter
57
Error message and Trouble Shooting