The pin definition of RS-485 is shown in Table 4-7. Different RS-485 connection
needs different set up of the terminal resistor.
• When single inverter is installed, the terminal resistor on its communication
module should be switched ON.
When multi-inverters in chain as shown in Figure 4-8, only the last inverter’s
terminal resistor must be switched ON.
Please refer to Table 4-8 for the terminal resister setting.
Pin Function
1 VCC (+12V)
2 GND
3 DATA+
4 DATA-
5 DATA+
6 DATA-
Table 4-7 : Definition of RS-485 pin
Figure 4-8 : Multi-inverter connection illustration
1 2 3 4 5 6
Data Format:
Baud rate: 9600, 19200 (default), or 38400
Data bits: 8
Stop bit: 1
Parity: N/A
RS485/USB
or
RS485/RS232
Terminal Resistor
120Ω(1/2W)
DATA+ to DATA-
4.4.1 RS-485 Connection
30
Wiring

Table of Contents