3.6.3 - Description of Outputs
CVIC output, PLC input wiring
Below are shown the two wiring configurations available for the relayed outputs of the CVIC:
A) The PLC 24 V is connected to the CVIC output
common
The PLC inputs do not receive external 24 V.
B) The CVIC 24 V is connected to the output common.
The PLC inputs do not receive 24 V from the CVIC.
All outputs are enabled at 1 and relayed in the controller with a common point (4) for all outputs.
Features of the contacts:
1A / 150V / 30W max. DC on resistive charge.
24 V
0 V
4
Output
common
24 V (17, 20)
Output
common
0 V (1, 16)
4
0 V
Outputs Name L H Factory
configuration
Comments
Cycle 1
acknowledgement
CYC1 x x Binary coding -weight 1- . The cycle
acknowledgement is sent back only if it
corresponds to a programmed cycle;
otherwise it is at "0".
Cycle 2
acknowledgement
CYC2 x x Binary coding -weight 2- . The cycle
acknowledgement is sent back only if it
corresponds to a programmed cycle;
otherwise it is at "0".
Cycle 4
acknowledgement
CYC4 x x Binary coding -weight 4- . The cycle
acknowledgement is sent back only if it
corresponds to a programmed cycle;
otherwise it is at "0".
Cycle 8
acknowledgement
CYC8 x x Binary coding -weight 8- . The cycle
acknowledgement is sent back only if it
corresponds to a programmed cycle;
otherwise it is at "0".
Ready READY x x x This signal is at "1" when the controller is in
working order.
In cycle INCYC x x x Response to the Start Cycle request. Drops
to "0" at end of cycle.
Global report OK ACCRP x x x Sent to the PLC when the cycle is over and
the global report is OK.
Global report NOK REJRP x x x Sent to the PLC when the cycle is over and
the global report is NOK.
Number of cycles OK NCYOK x x x This signal switches to "1" when the number
of cycles run with an Accept report is equal
to the programmed number of cycles OK.
Synchronisation SYNC x 0.3
Torque report OK TOROK x Sent to the PLC when the cycle is over and
the torque report is OK.
Torque report NOK TORNOK x Sent to the PLC when the cycle is over and
the torque report is NOK.
Angle report OK ANGOK x Sent to the PLC when the cycle is over and
the angle report is OK.