3.7 - «PERIPHERALS» Menu
3.7.1 - «SERIAL PORT» Menu
The serial port is used for the following functions:
♦ Downloading to PC,
♦ Bar code and report output,
♦ Printing the results in order of occurrence (ASCII),
♦ Automatic calibration with the DELTA4000 measuring unit (no programming is required).
- Downloading to PC
- Controller
The parameters used for downloading to the PC are as follows:
RS232/RS422:
RS232 default standard type used for connecting a PC and a single controller
RS422 used in a network configuration only.
Baud rate from 300 to 19,200 Bauds, 7 or 8 data bits, 1 or 2 stop bits, no parity/even/odd.
Default values: 19,200 Bauds, 8 data bits, 1 stop bit, no parity.
Slave # 0-254. In a network configuration, the PC is connected to several controllers at the same
time.
For further information about the network connection, refer to the «CVIPC» Operator’s
Manual.
- Self-contained MODCVIC
For the MODCVIC module, the switching of the communications standard RS232 / RS422 is automatic
depending on the address selected by the rotary switches:
- address 0 implies standard RS232 for the connection of a PC and a single controller.
- any other address selected implies standard RS422 for a network connection.
The other parameters are set to:
- 19,200 bauds.
- 8 data bits.
- 1 stop bit.
- no parity.
They cannot be programmed by the PC.
In the case of a network connection, the «Intermediate» or «end of line» differentiation is obtained by resistance
wiring in the connectors of the network cable. (See wiring diagrams).
3.7.2 - «REPORT OUTPUT» Menu
The report is printed according to the following parameters:
Format PC2/PC3/PC4/Specific/PC5A/PC5B/PC5C.
Upon request at end of cycle.
(See «Printing format of tightening results» in Appendix)