50 ECB-VAVS Preloaded Applications
Configuration Parameters for the VAV
Parameter Valid Choices Descriptions
CODE VAV Box Code VAV Box Configuration Code Entry
DUCT HT Duct Heater Stages
1 NONE No Duct Heater Reheat
2 1 ST Duct Heater Reheat on Heat Source 1
3
2 St
Duct Heater Reheat on Heat Sources 1
& 2
HTPRIO Heat Priority
1 DUCT Duct Heating 1st
2 PERI Perimeter Heating 1st
3 BOTH Both Heating Simultaneously
DUAL MAX Dual Maximum Flow Control
1 NO
Box is not using Dual Maximum Control
Settings
2 YES
Box is using Dual Maximum Control
Settings
HWREHEAT Hot Water Reheat
1 NO Duct Heater is not Hot Water Coil
2 YES Duct Heater Reheat by Hot Water Coil
VVTMODE VVT Mode
1 NO Box is using Flow Input
2 YES Box is not Using Flow Input
FLOATVLV Floating Valve Drive Time
EDIT
1
95 S
95 seconds drive time
2
125 S
125 seconds drive time
3
150 S
150 seconds drive time
4
25 S
25 seconds drive time
5
30 S
30 seconds drive time
6
50 S
50 seconds drive time
7
60 S
60 seconds drive time
8
Custom
Drive time controlled by
CustomFloatTime
PWMVLV
Pule Width Modulation Valve
Period
1 25.5 0.1 to 25.5 seconds
2 5.2 0.1 to 5.2 seconds