28 ECL-PTU-207 Preloaded Applications
nciComSensorConfig (nviFP45)
This configuration property can be used to rescale the heating cooling load of the different equip-
ments.
Field Description
MinCoolSP Unused
MaxCoolSP Unused
MinHeatSP Unused
MaxHeatSP Unused
ComSensorSpType unused
ComSensorDisplay
Defines the value to be displayed by the EC-Smart-Vue (SpaceTemp, MidSetpoint,
SetPtOffset, EffectSp)
ComSensor1Lock
Defines the available menus level on the EC-Smart-Vue (Full Access, Sp & Overrides, Sp
Only, No Access)
ComSensor2Lock Unused
ComSensor1DegF Unused
ComSensor2DegF Unused
DisplaySpaceCO2
Used to enable the display of the space CO2 concentration on the EC-Smart-Vue rolling
display
DisplayOutdoorTemp Unused
DisplaySpaceRH Used to enable the display of the space air humidity on the EC-Smart-Vue rolling display
Reserved1 Unused
Reserved2 Unused
Reserved3 Unused
Field Name Field Name Max Value Max Value
MinCoolSP 15.5°C 32.5°C 20°C
MaxCoolSP 15.5°C 32.5°C 26°C
MinHeatSP 12.5°C 29.5°C 16°C
MaxHeatSP 12.5°C 29.5°C 22°C
ComSensorSpType 0(coolheatsp) 2(midsetpoint) 1(spoffset)
ComSensorDisplay 0(spacetemp) 3(effectsp) 0(spacetemp)
ComSensor1Lock 0(Full Access) 3(No Access) 0(Full Access)
ComSensor2Lock 0(Full Access) 3(No Access) 0(Full Access)
ComSensor1DegF 0 1 0
ComSensor2DegF 0 1 0
DisplaySpaceCO2 0 1 0
DisplayOutdoorTemp 0 1 0
DisplaySpaceRH 0 1 0
Reserved1 0 1 1
Reserved2 0 1 1
Reserved3 0 1 0
ID Units Default Value
nviFP45 UNVT_comsensor_1to2_config N/A
Variables