37ECL-PTU-207 Preloaded Applications
Boolean Constants
FreeCoolingEnable (ConstantBool1)
This variable is used to enable free cooling via the fresh air damper.
ID Units Valid Range Default Value
Constant Boolean 1 TRUE/FALSE N/A FALSE
EnableRoomUnocc (ConstantBool2)
This variable is used to configure the behavior of RoomOccupancy when the OccupancyCmd is set to
unoccupied.
When this variable is set to TRUE, the RoomOccupancy (BV2), will be set to Unoccupied on the re-
ception of an unoccupied command from nviSchedule_1.
ID Units Valid Range Default Value
Constant Boolean 2 TRUE/FLSE N/A TRUE
nviFanSpeedCmdDigital (ConstantBool3)
This variable is used to configure the behavior of the fan speed signal when receiving fan speed com-
mand override from nviFanSpeedCmd.
When this value is set to TRUE, the value received from nviFanSpeedCmd will be considered 3 fan
speed operation commands.
See nviFanSpeedCmd for more information on this configuration parameter.
ID Units Valid Range Default Value
Constant Boolean 3 TRUE/FALSE N/A TRUE
HeatValveConfig (ConstantBool4)
This variable is used to configure the operating mode of the heating valve.
ID Units Valid Range Default Value
Constant Boolean 4 NormOpen/NomClose N/A NormClose (FALSE)
CoolValveConfig (ConstantBool5)
This variable is used to configure the operating mode of the cooling or change-over valve
ID Units Valid Range Default Value
Constant Boolean 5 NormOpen/NomClose N/A NormClose (FALSE)
Variables

Table of Contents

Other manuals for Distech Controls ECL-PTU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls ECL-PTU Series and is the answer not in the manual?

Distech Controls ECL-PTU Series Specifications

General IconGeneral
BrandDistech Controls
ModelECL-PTU Series
CategoryController
LanguageEnglish

Related product manuals