93ECL-PTU-207 Preloaded Applications
Digital Input 6
Parameter Default Valid
Choices
Description
DI6
(EC5)
0 UNUSED DI5 is not used
X 1 AUX CONT NO Auxiliary contact is normally open
2 AUX CONT NC Auxiliary contact is normally closed
3 CHG OVER HEAT Changeover contact ( TRUE = Heat / FALSE = Cool)
4 CHG OVER COOL Changeover contact (TRUE = Cool / FALSE = Heat)
5 OCC SENSOR NO Occupancy sensor is normally open
6 OCC SENSOR NC Occupancy sensor is normally closed
Table30: Digital Input 6
Tables of configuration codes