35ECL-PTU-207 Preloaded Applications
nvoDewPointSensor (nvoFP22)
This output network variable is used to monitor the actual dew point sensor status used by the con-
troller.
The dewpoint status is calculated using the following priority order:
£ Valid value received by nviDewPtSensor
£ Hardware input configured for dew point sensor (Digital Input)
If none of these are valid, nvoDewPtSensor is by default set to Enable and will output ‑1.0.
State Value Cooling Valve
0 n/a Enable
1 0 Disable
1 >0 Disable
0xFF n/a Enable
ID Units Valid Range Default Value
nvoFP22 SNVT_switch N/A N/A
nvoWindowContct (nvoFP24)
This output network variable is used to monitor the window contact status of the space comfort con-
troller.
State Value Window Contact
0 n/a Close
1 0 Close
1 > 0 Open
0xFF n/a Close
ID Units Valid Range Default Value
nvoFP24 SNVT_switch N/A N/A
nvoAuxContact (nvoFP25)
This output network variable is used to monitor the status of an auxiliary contact wired to the space
comfort controller.
State Value Contact Status
Contact Status Contact Status Contact Status
Contact Status Contact Status Contact Status
Contact Status Contact Status Contact Status
Contact Status Contact Status Contact Status
ID Units Valid Range Default Value
nvoFP25 SNVT_switch N/A N/A
nvoEcoVue (nvoFP26)
This output network variable can be used to display the actual ECO-Vue of the unit. This variable is
not used in this program.
ID Units Valid Range Default Value
nvoFP26 SNVT_energy_efficient N/A N/A
Variables