36 ECL-PTU-207 Preloaded Applications
nvoSlaveInfo (nvoFP27)
This output is used to send information from a slave controller.
The different information received from the slave controller will be processed by the master controller
to calculate the different operating mode and functions of the master controller.
In a master/slave scenario, this variable will be bound to nviSlaveInfo of the master controller.
The nvoSlaveInfo of the master controller must be bound to its own nviSlaveInfo to make sure that the
information is processed in the calculation.
Field Description
SpaceTemp Local Space Temperature
SetpointOffset Local Setpoint Offset
FanSpeedCmd Local Fan Speed Command
LightLevel Local light level of EC-Multi-Sensor with nciLightLoopCfg/ReflexFactor
Occupancy Local Occupancy from EC-Remote
Motion Local Motion detection
Window Local Window Contact Information
SetpointOffsetUpdate Local Setpoint Offset Update
FanSpeedCmdUpdate Local Fan Speed Command Update processed.
OccupanyUpdate Local Occupancy Update
GroupUpdate Local EC-Remote Group Command Update
Group1-8 EC-Remote remote control group commands (Light/Blind/)
ID Units Valid Range Default Value
nvoFP27 SNVT_SlaveInfo N/A N/A
Variables

Table of Contents

Other manuals for Distech Controls ECL-PTU Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Distech Controls ECL-PTU Series and is the answer not in the manual?

Distech Controls ECL-PTU Series Specifications

General IconGeneral
BrandDistech Controls
ModelECL-PTU Series
CategoryController
LanguageEnglish

Related product manuals